本题答案:A。<\/div>"},{"id":624,"title":"灭火救援窗的窗口下沿距室内地面不宜大于( )m。","stem":"","options":"0.8^*@*^0.9^*@*^1^*@*^1.2","answer":"D","explanation":"厂房、仓库、公共建筑的外墙应每层设置可供消防救援人员进入的窗口。窗口的净高度和净宽度分别不应小于0.8m和1.0m,下沿距室内地面不宜大于1.2m,间距不宜大于30m,且每个防火分区不应少于2个,设置位置应与消防车登高操作场地相对应。所以,根据题意,正确答案为D。"},{"id":14631,"title":"防止液体流散的其中一种做法就是在桶装仓库门洞处修筑慢坡,该慢坡高度一般不小于()。","stem":"","options":"50mm^*@*^100mm^*@*^150mm^*@*^300mm","answer":"C","explanation":"防止液体流散的其中一种做法就是在桶装仓库门洞处修筑慢坡,该慢坡高度一般不小于150mm"},{"id":9261,"title":"地铁的安全出口应分散设置,当同方向设置时,两个安全出口通道口部之间的净距不应小于()m。","stem":"","options":"5^*@*^8^*@*^10^*@*^12","answer":"C","explanation":"地铁的安全出口应分散设置,当同方向设置时,两个安全出口通道口部之间的净距不应小于10m。"},{"id":14733,"title":"下列不属于湿式报警阀组漏水原因的是( )。","stem":"","options":"限流装置过滤网被堵塞^*@*^阀瓣密封垫老化或者损坏^*@*^排水阀门未完全关闭^*@*^报警管路测试控制阀渗漏","answer":"A","explanation":""},{"id":2149,"title":"为保证疏散通道不受烟气侵害以及人员安全疏散,发生火灾时,从安全性的角度出发,高层建筑内可分为四个安全区。走道属于( )。","stem":"","options":"第一类安全区^*@*^第二类安全区^*@*^第三类安全区^*@*^第四类安全区","answer":"C","explanation":"为保证疏散通道不受烟气侵害以及人员安全疏散,发生火灾时,从安全性的角度出发,高层建筑内可分为四个安全区:第一类安全区为防烟楼梯间、避难层;第二类安全区为防烟楼梯间前室、消防电梯间前室或合用前室;第三类安全区为走道;第四类安全区为房间。"},{"id":8789,"title":"闭式自动喷水灭火系统可分为( )类。","stem":"","options":"三^*@*^四^*@*^五^*@*^六","answer":"B","explanation":"本题考查的是自动喷水灭火系统的分类。自动喷水灭火系统根据所使用喷头的型式,分为闭式自动喷水灭火系统和开式自动喷水灭火系统两大类。其中,闭式系统又可分为湿式自动喷水灭火系统、干式自动喷水灭火系统、预作用自动喷水灭火系统、自动喷水-泡沫联用系统。开式系统分为雨淋系统和水幕系统。故,本题选B。"},{"id":2396,"title":"当A级或B级电子信息系统机房位于其他建筑物内时,在主机房与其他部位之间应设置耐火极限不低于( )的隔墙,隔墙上的门应采用甲级防火门。","stem":"","options":"2h^*@*^2.5h^*@*^3h^*@*^3.5h","answer":"A","explanation":"当A级或B级电子信息系统机房位于其他建筑物内时,在主机房与其他部位之间应设置耐火极限不低于2h的隔墙,隔墙上的门应采用甲级防火门。
本题答案:A。<\/div>"},{"id":8797,"title":"当消防电源由自备应急发电机组提供备用电源时,消防用电负荷为一级或二级的要设置自动和手动启动装置,并在()s内供电。","stem":"","options":"30^*@*^60^*@*^90^*@*^120","answer":"A","explanation":"
\n\t当消防电源由自备应急发电机组提供备用电源时,消防用电负荷为一级或二级的要设置自动和手动启动装置,并在30s内供电;当采用中压柴油发电机组时,在火灾确认后要在60s内供电。\n<\/p>"},{"id":8605,"title":"采用流量系数K =80快速响应喷头的系统,喷头的布置应符合()场所的有关规定。","stem":"","options":"轻危险级Ⅰ级^*@*^中危险级Ⅰ级^*@*^中危险级Ⅱ级^*@*^严重危险级Ⅰ级","answer":"B","explanation":"
\n\t采用流量系数K = 80快速响应喷头的系统,喷头的布置应符合中危险级Ⅰ<\/span>级场所的有关规定。\n<\/p>"},{"id":764,"title":"充实水柱是指由水枪喷嘴起至射流90%的水柱水量穿过直径为( )圆孔处的一段射流长度。","stem":"","options":"250mm^*@*^300mm^*@*^350mm^*@*^380mm","answer":"D","explanation":"充实水柱是指由水枪喷嘴起至射流90%的水柱水量穿过直径为380mm圆孔处的一段射流长度。本题答案:D。<\/div>"},{"id":1417,"title":"液化石油气加气站采用地上储罐的,其固定式消防冷却水系统的冷却水供给强度不应小于( )。","stem":"","options":"0.15L\/(㎡
·<\/strong>s)^*@*^0.30L/(㎡·<\/strong>s)^*@*^0.50L/(㎡·<\/strong><\/strong>s)^*@*^1.00L\/( ㎡·<\/strong>s)","answer":"A","explanation":"总容积超过50m3的地上储罐应设置固定式消防冷却水系统,其冷却水供给强度不应小于0.15L\/(㎡·<\/strong>s)。本题答案:A。<\/div>"},{"id":11912,"title":"某大型焦化场,根据实际需要划分生产区,储存区(煤气、煤焦油及副产品),生产辅助区,行政办公区和生活区,该地区全年最小频率风向为东南方向,因此,储存区宜布置在厂区的( )。","stem":"","options":"东南侧^*@*^西北侧^*@*^东北侧^*@*^西南侧","answer":"A","explanation":"液化石油气储罐区宜布置在本单位或本地区全年最小频率风向的上风侧,并选择通风良好的地点独立设置。易燃材料的露天堆场宜设置在天然水源充足的地方,并宜布置在本单位或本地区全年最小频率风向的上风侧。
本题答案:A。<\/div>"},{"id":9147,"title":"某大型的上市公司新建了一座A级计算机房,那么该机房的火灾自动报警系统应按()级保护对象的要求进行设置。","stem":"","options":"一^*@*^二^*@*^三^*@*^四","answer":"A","explanation":"本题考查的是信息机房的火灾自动报警系统。A级计算机房及面积大于140m

的信息机房的火灾自动报警系统应按一级保护对象的要求进行设置,面积小于140m

的B级计算机房的火灾自动报警系统应按二级保护对象的要求进
行设置。故本题的答案为选项A。<\/span>"}]